The Air Distribution Simulation inside the Glass Showroom Using Radiant Floor and Convection Cooling Systems
Main Article Content
Abstract
This research focused on finding velocity and temperature distributions of air inside a glass showroom since showroom demands are growing according to electrical vehicle makers are extended. The showroom was equipped with convection (traditional) and radiant floor cooling systems. The standard k-epsilon model of ANSYS Fluent was utilize to investigate 3 cases of the cooling systems; only traditional, only floor, and both systems. The results showed that the velocity distributions of the first and third cases were related to each other. The distribution in the second case was the smoothest because no forced convection occurred. The average temperatures of 3 cases were 24.21°C, 22.28°C and 20.66°C, respectively. This research could provide important information in using both systems in any showrooms. When chilled water available, the radiant floor cooling system should be used to take sensible heat loads and the traditional system should be used to take fluctuating latent heat loads.
Article Details

This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License.
This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike 4.0 International License.
References
Odyjas A, Górka A. Simulations of floor cooling system capacity. In: Proceedings of the 12th International Conference on Modern Building Systems. 2013; 101-108.
Wibron E, Ljung AL, Lundström TS. Comparing performance metrics of partial aisle containments in hard floor and raised floor data centers using CFD. Paper presented at: ASHRAE Annual Conference. 2019; Kansas City, MO.
Snidvongs S. The design and implementation of parabolic trough 300 kW power plant for soft-land, medium insolation and moist weather country. In: Proceedings of the ASME Conference. 2020. Paper No. ASME2006-99008.
Samsudin SSA, Shaari AM, Abdullah K, Batcha MFM. Potential of utilizing solar chimney as an energy efficiency measure in Malaysian hospitals. J Build Perform. 2020;11(2):102-113.
Lopez NS, Galeos SK, Calderon BR, Dominguez DR, Uy BJ, Iyengar R. Computational fluid dynamics simulation of indoor air quality and thermal stratification of an underfloor air distribution system (UFAD) with various vent layouts. Energy Rep. 2021;7:465-477.
Nawale PR, Mule AA, Powar SB, Kothmire PP. Enhancement technique of heat transfer using inserted twisted tape. Mater Today Proc. 2021;46:11823-11827.
Akbarpoor AM, Haghighi Poshtiri A, Biglari F. Performance analysis of domed roof integrated with earth-to-air heat exchanger system to meet thermal comfort conditions in buildings. J Build Perform. 2021;12(4):204-217.
Jafari S, Kalantar V. Numerical simulation of natural ventilation with passive cooling by diagonal solar chimneys and windcatcher and water spray system in a hot and dry climate. Renew Energy. 2022;186:955-971.
Nuitchanthuek T, et al. The capability comparison of the radiant floor cooling system in the evaporative cooling greenhouse in the daytime and nighttime. In: Proceedings of the 36th Conference of the Mechanical Engineering Network of Thailand; 2022. p. 924-931.
Pawlak F, Koczyk H, Górka A. 3D numerical model for transient simulations of floor cooling capacity and thermal comfort in a thermally heterogeneous room. Energy Rep. 2023;9:1167-1180.
Khovalyg D, Mudry A, Keller T. Prefabricated thermally activated fiber-polymer composite building slab P-TACS: Toward the multifunctional and prefabricated structural elements in buildings. J Build Perform. 2023;14(1):78-89.
Charoenpornpanich J. Radiant floor cooling. In: Proceedings of the Air Conditioning Engineering Association of Thailand. 2016. p. 119-126.
Janthasri P, Pramuanjaroenkij A, Kakaç S, Chungchoo C, Ngamvilaikorn T. Energy consumption comparison of two cooling systems equipped with the heat exchangers in different agricultural postharvest storage conditions. Therm Sci Eng Prog. 2024;48:102419.
Janthasri P, Arunachalam V, Singh M. Radiant floor and traditional cooling system applications in agricultural product storages. J Res Appl Mech Eng. 2024;12(2):021-014.
ASHRAE. Thermal environmental conditions for human occupancy. Approved by ASHRAE and the American National Standards Institute on July 31, 2020. Atlanta, GA: ASHRAE; 2020.
Anchasa, P. Radiant cooling system for energy management in buildings. In: Association of Cooling and Air-Conditioning Engineers of Thailand. 2020:81-90.
Lim, J-H., Kim, K-W. ISO 11855 - The international standard on the design, dimensioning, installation and control of embedded radiant heating and cooling systems. REHVA Journal. 2016:46-53.