ENERGY SAVING BY SOLAR COLLECTOR IN SRINAGARIND HOSPITAL
Main Article Content
Abstract
Srinagarind Hospital was implemented by various energy conservation measures such as electric, lighting, air conditioning and heating. For heat measure, installed solar collector system for 5 ton/hr boiler. The system an installation on the roof has 310 panels evacuated tubular with 15,000 liters of storage, the temperature in the range of 70-90 °C. The study collected data of variables according to the actual load in accordance with compared in the period 2014 and 2016.
The result, both before and after has a steam 1,787.14 and 1,791.41 kg-s/hr, and the index of steam production per fuel oil was 14.35 and 15.61 kg-s/l then the amount of fuel consumption was lower than the original 8.01%, It was found that the energy saving is 77,285 liters per year and a payback period within 6.81 years.