Analysis of potential energy and cost savings of replacing air-cooled chillers with water-cooled chillers: A case study in hotel building in tropical climate

Main Article Content

Arka Dwinanda Soewono
https://orcid.org/0000-0003-1606-0203
Ivan Agustinus Kusmanto
Marten Darmawan
Sheila Tobing

Abstract

Selecting the type of chillers to be used in commercial buildings is critical considering their high energy consumption, which consequently requires the use of chillers with higher efficiency in order to improve the energy efficiency of buildings and reduce their carbon footprint. Through a case study in a commercial resort, this research presents an energy consumption analysis of the replacement of air-cooled chillers with water-cooled chillers. The energy savings were calculated based on not only the simulation software but also the actual energy consumption data after the installation of the water-cooled chillers. The energy analysis indicated that the use of water-cooled chillers to substitute the air-cooled chillers in the resort resulted in energy saving of around 17.5% with a reduction of 2860 tonnes of CO2 equivalent emission per year. Meanwhile, the cost analysis showed that the life-cycle cost of the water-cooled chillers is around 13.4% less. These findings demonstrate the potential of using water-cooled chillers as a replacement for air-cooled chillers in existing commercial buildings to reduce energy consumption and its associated carbon emission without compromising the buildings’ indoor comfort. This option can be an appeal to building owners as it has some evident economic benefits.

Article Details

How to Cite
Soewono, A. D., Kusmanto, I. A., Darmawan, M., & Tobing, S. (2023). Analysis of potential energy and cost savings of replacing air-cooled chillers with water-cooled chillers: A case study in hotel building in tropical climate. Engineering and Applied Science Research, 50(4), 372–381. Retrieved from https://ph01.tci-thaijo.org/index.php/easr/article/view/252559
Section
ORIGINAL RESEARCH

References

Lin M, Afshari A, Azar E. A data-driven analysis of building energy use with emphasis on operation and maintenance: a case study from the UAE. J Clean Prod. 2018;192:169-78.

Xiong W, Wang J. A semi-physical static model for optimizing power consumption of HVAC systems. Control Eng Pract. 2020;96:104312.

Sala-Cardoso E, Delgado-Prieto M, Kampouropoulos K, Romeral L. Predictive chiller operation: a data-driven loading and scheduling approach. Energy Build. 2020;208:109639.

Yu J, Liu Q, Zhao A, Qian X, Zhang R. Optimal chiller loading in HVAC system using a novel algorithm based on the distributed framework. J Build Eng. 2020;28:101044.

Saidur R, Hasanuzzaman M, Mahlia TMI, Rahim NA, Mohammed HA. Chillers energy consumption, energy savings and emission analysis in an institutional buildings. Energy. 2011;36(8):5233-8.

Lin CM, Wu CY, Tseng KY, Ku CC, Lin SF. Applying two-stage differential evolution for energy saving in optimal chiller loading. Energies. 2019;12(4):622.

Yu FW, Chan KT, Sit RKY, Yang J. Review of standards for energy performance of chiller systems serving commercial buildings. Energy Procedia. 2014;61:2778-82.

Zhang D, Luh PB, Fan J, Gupta S. Chiller plant operation optimization with minimum up/down time constraints. IEEE Robot Autom Lett. 2018;3(1):9-15.

Liu PL, Chuang BS, Lee WS, Yeh PL. An analytical solution of the optimal chillers operation problems based on ASHRAE guideline 14. J Build Eng. 2022;46:103800.

Al-Waked R, Nasif MS, Groenhout N, Partridge L. Energy performance and CO2 emissions of HVAC systems in commercial buildings. Buildings. 2017;7(4):84.

Yu FW, Chan KT, Sit RKY. Carbon emissions of chiller systems in Hong Kong hotels under climate change. Strateg Plan Energy Environ. 2014;34(2):39-64.

Yu FW, Chan KT, Sit RKY. Environmental benefits of sustainable chiller system under climate change. Int J Sustain Build Technol Urban Dev. 2014;5(2):109-14.

Chaerun Nisa E, Kuan YD. Comparative assessment to predict and forecast water-cooled chiller power consumption using machine learning and deep learning algorithms. Sustainability. 2021;13(2):744.

Wang H, Lei Z, Zhang X, Zhou B, Peng J. A review of deep learning for renewable energy forecasting. Energy Convers Manag. 2019;198:111799.

Ho WT, Yu FW. Chiller system optimization using k nearest neighbour regression. J Clean Prod. 2021;303:127050.

Zheng Z, Li J, Duan P. Optimal chiller loading by improved artificial fish swarm algorithm for energy saving. Math Comput Simul. 2019;155:227-43.

Alonso S, Morán A, Prada MÁ, Reguera P, Fuertes JJ, Domínguez M. A data-driven approach for enhancing the efficiency in chiller plants: a hospital case study. Energies. 2019;12(5):827.

Yan C, Cheng Q, Cai H. Life-cycle optimization of a chiller plant with quantified analysis of uncertainty and reliability in commercial buildings. Appl Sci. 2019;9(8):1548.

Yu FW, Chan KT. Optimization of water-cooled chiller system with load-based speed control. Appl Energy. 2008;85(10):931-50.

Jiang X, Long W, Li M. Optimum control strategy for all-variable speed chiller plant. J Cent South Univ. 2011;18:573-9.

Furlong J, Crowther H. Optimizing chillers and towers. ASHRAE J. 2004;46(7):34-45.

Hsu CN, Wang SH. Evaluating the performance of water chillers equipped with constant- or variable-frequency centrifugal compressors. Processes. 2021;9(6):1039.

Trautman N, Razban A, Chen J. Overall chilled water system energy consumption modeling and optimization. Appl Energy. 2021;299:117166.

Yu FW, Chan KT, Sit RKY, Yang J. Critique of the design and operation of sustainable air-cooled chillers in commercial buildings. Energy Eng. 2015;112(3):55-79.

Kim SH, Kim DG. Survey study on optimal cooling equipment capacity in office buildings. J Archit Inst Korea. 2007;23(8):247-54.

Ma K, Zhao T, Shen D, Liu M. Web based chiller plant optimal control-a case study. Procedia Eng. 2017;205:967-74.

Ha J, Cho S, Kim H, Song Y. Annual energy consumption cut-off with cooling system design parameter changes in large office buildings. Energies. 2020;13(8):2034.

Dahlhausen M, Heidarinejad M, Srebric J. Building energy retrofits under capital constraints and greenhouse gas pricing scenarios. Energy Build. 2015;107:407-16. https://doi.org/https://doi.org/10.1016/j.enbuild.2015.08.046.

Partridge LE, Loughnane EJ. Committed carbon—upgrading existing buildings. Struct Des Tall Spec Build. 2008;17(5):989-1002.

Kaya D, Alidrisi H. Energy savings potential in air conditioners and chiller systems. Turkish J Electr Eng Comput Sci. 2016;24(3):935-45.

Yatim A, Prima JA, Jofansya MA, Alhamid MI, Budihardjo, Lubis A. Performance of oil-free water-cooled chiller for a shopping center air conditioning system. IOP Conf Ser Earth Environ Sci. 2021;673:12010.

Lyu W, Wang Z, Li X, Xin X, Chen S, Yang Y, et al. Energy efficiency and economic analysis of utilizing magnetic bearing chillers for the cooling of data centers. J Build Eng. 2022;48:103920.

Anandh N, Kumar P. A case analysis on energy savings and efficiency improvement of a chiller plant in a luxury hotel building. Int Energy J. 2021;21(4):447-56.

Marjianto A, Hafthirman, Darmanto PS. Energy and cost saving potential of hotel air conditioning using magnetic bearing chiller in Jakarta. Int J Innov Mech Eng Adv Mater. 2021;3(1):1-11.

Yu FW, Chan KT, Sit RKY, Yang J. Performance evaluation of oil-free chillers for building energy performance improvement. Procedia Eng. 2015;121:975-83.

Naguib R. The changing landscape of chillers’ energy efficiency. Energy Eng. 2011;108(4):25-45.

Naguib R. Total cost of ownership: for air-cooled and water-cooled chiller systems. ASHRAE J. 2009;5(4):42-8.

Howell RH, Land DW, Scheideman ED. Air-cooled HVAC retrofit: safe bet for Vegas schools. ASHRAE J. 2004;46(5):28-32.

Hvac A, Khalil E. Energy evaluations between air-cooled vs water-cooled cooling systems in egyptian private buildings. 3rd International Energy Conversion Engineering Conference; 2005 Aug 15-18; San Fransisco, USA. San Fransisco: American Institute of Aeronautics and Astronautics; 2005.

Azmi R, Maslahat P, Wahono JW. The carbon footprint from the power plant in Indonesia and renewable energy supply for reduce the carbon emission. IOP Conf Ser Earth Environ Sci. 2022;997:12008.

Yik FWH, Lai JHK, Fong NK, Leung PHM, Yuen PL. A case study on the application of air- and water-cooled oil-free chillers to hospitals in Hong Kong. Build Serv Eng Res Technol. 2011;33(3):263-79.

Tam LS, Lau KC, Shek LC. Achievements and participation of the pilot scheme for fresh water evaporative cooling towers. Proc. of Symposium on Solution, Breakthrough & Technical Approach for Wider User of Water-cooled Air Conditioning System; 2006 Dec 8; Hong Kong. Hong Kong: Association of Energy Engineers; 2006. p. 1-9.

Gao Z, Liu H, Xu X, Xiahou X, Cui P, Mao P. Research progress on carbon emissions of public buildings: a visual analysis and review. Buildings. 2023;13(3):677.

Dakwale VA, Ralegaonkar RV. Review of carbon emission through buildings: threats, causes and solution. Int J Low-Carbon Technol. 2012;7(2):143-8.

Abeydeera LH, Karunasena G. Carbon emissions of hotels: the case of the Sri Lankan hotel industry. Buildings. 2019;9(11):227.