Study of Problem and Effect Mitigation Technique of Unbalance Capacitance in 500 kV Single Phase Transformers

Authors

  • Suthat Suksagoolpanya Department of Electrical Engineering, School of Engineering, King Mongkut’s Institute of Technology Ladkrabang
  • Norasage Pattanadech Department of Electrical Engineering, School of Engineering, King Mongkut’s Institute of Technology Ladkrabang

DOI:

https://doi.org/10.55003/ETH.410108

Keywords:

Power transformer, Capacitance, Unbalance voltage, Capacitor voltage transformer

Abstract

This article presents the study of the effect of unbalanced stray capacitance in single-phase 500 kV power transformers and establishes the mitigation technique. The power transformers were operated in Wang Noi Substation for transmitting the electrical power. There are 3 units of single-phase power transformer. Previously, a transformer of
phase B failed after being serviced for several years. Thus, the new power transformer was ordered instead of the failed one. However, once the new system had been operated, the hotspots at the surge arrester of tertiary winding (22 kV) were found and the unbalance of phase voltages was observed, resulting in overvoltage as a root cause of the problem. Once a thorough investigation was done, it was found that there was an effect of unbalanced stray capacitance between tertiary winding and ground core since the new power transformer has some different designs compared with the remaining. Hence, the mitigation technique was performed by adding the capacitor parallel to the tertiary winding until the voltage balance was achieved. Simulation with the PSCAD program was performed to determine the optimum value for additional capacitors, i.e., voltage balance, using an iterative method. In this article, the capacitors used for additional were capacitor voltage transformers, which have been installed. As a result of the troubleshooting, the voltage at the 22 kV bus was more balanced as well as not causing overvoltage, and the hotspots at the surge arrester of tertiary winding were not detected resulting in gaining the stability and reliability of using these transformers.

References

M. J. Heathcote, “Transformer theory,” in J & P Transformer Book, 13th ed., Woburn, MA, USA: Butterworth-Heinemann, 2018, ch. 1, pp. 1–13.

F. Zhu and B. Yang, “Introduction,” in Power Transformer Design Practices, Boca Raton, FL, USA: CRC Press, 2021, ch. 1, pp. 1–20.

K. R. M. Nair, “Transformer Design,” in Power and Distribution Transformers: Practical Design Guide, Boca Raton, FL, USA: CRC Press, 2021, ch. 1, pp. 1–6.

A. Küchler, “Introduction,” in High Voltage Engineering, Heidelberg, Germany: Springer-Verlag GmbH, 2018, ch. 1, pp. 1–4.

E. Kuffel, W. S. Zaengl and J. Kuffel, “Introduction,” in High Voltage Engineering, 2nd ed., Woburn, MA, USA: Butterworth-Heinemann, 2000, ch. 1, pp. 1–7.

S. Sangkasaad, “Introduction,” in High Voltage Engineering, 3rd Ed., Bangkok, Thailand: Chulalongkorn University Press, 2006, ch. 1, pp. 1–7. (in Thai)

L. Tang and P. Zhao, “Tertiary Voltage Unbalance Compensation for 500kV Single Phase Autotransformer Banks,” in 2018 IEEE/PES Transmission and Distribution Conference and Exposition (T&D), Denver, CO, USA, 2018, pp. 1¬6, doi:10.1109/TDC.2018.8440349.

Y. Yang, J. Zhang, Y. Jin and B. Wei, “Analysis of imbalanced voltage on 35 kV side after single phase replacement of 500 kV transformer,” Journal of Physics: Conference Series, vol. 2369, 2022, Art. no. 012065, doi: 10.1088/1742-6596/2369/1/012065.

L. Mosi and S. Zhiyuan, “Research on Single-phase Replacement of 500 kV Transformer based on PSCAD,” in 6th International Conference on Energy and Environmental Protection (ICEEP 2017), Zhuhai, China, 2017, pp. 937¬941, doi: 10.2991/iceep-17.2017.162.

P. M. Anderson, “Pilot Protection Systems,” in Power System Protection, Hoboken, NJ, USA: John Wiley & Sons, Inc., 1999, ch. 13, pp. 469–530.

K. Chayakulkheeree. (2016). EEG456 Electrical Power System Protection and Relays [Lecture note]. Available: http://eestaff.kku.ac.th/~sa-nguan/192424/%A1%D2%C3%BB%E9%CD%A7%A1%D1%B9%C3%D0%BA%BA%E4%BF%BF%E9%D2%A1%D3%C5%D1%A7_%C3%C8_%A1%D5%C3%B5%D4.pdf

Manitoba HVDC Research Centre, Manitoba, Canada. Power Systems Computer Aided Design User’s Guide, (2018). Accessed: August 1, 2023. [Online].Available:https://www.pscad.com/knowledge-base/download/pscad_manual_v4_6.pdf.

Downloads

Published

2024-03-25

How to Cite

[1]
S. . Suksagoolpanya and N. . Pattanadech, “Study of Problem and Effect Mitigation Technique of Unbalance Capacitance in 500 kV Single Phase Transformers”, Eng. & Technol. Horiz., vol. 41, no. 1, p. 410108, Mar. 2024.

Issue

Section

Research Articles