Rectangular in Twisted Tape Economizer Shell and Tube

Main Article Content

อุทัย ผ่องรัศมี
เสนีย์ ศิริไชย
อนุชา สายสร้อย
สำรวจ อินแบน

Abstract

This paper presents the effects of insertion of twisted tape on heat transfer performance a shell-and tube heat exchanger recovering a waste heat from an once-through boiler. The heat exchanger consisted of tube of 0.033 m outside diameter and 34 m total length, corresponding to total heat transfer area of 3.55 m2. The twisted-tape with rectangularshape hole with twist ratio (y/w) of 3 and total area of 0.09 m2 was inserted in the heat exchange tube. As revealed by the experiential results, at exhaust gas speed of 5 m/s, the heats of 429 kW and 212.82 kW were found at outer and inner surfaces of tube, respectively, ensuring the heat transfer coefficients of 5,470 W/m2ºC  and 24.82 W/m2ºC and corresponding pressure drops were 28.77 Pa and 5.34 Pa. The performance of the heat exchange was 0.6. As a result, energy saving cost of 136,084 Baht/year was achievable, leading to quite short simple payback period of 1.1 year. These operating conditions were recommended/suitable for the once-though boiler generating steam at 500 kg/h at the maximum pressure of 7 kg/cm2

Article Details

How to Cite
ผ่องรัศมี อ. ., ศิริไชย เ. ., สายสร้อย อ. ., & อินแบน ส. . (2015). Rectangular in Twisted Tape Economizer Shell and Tube. KKU Science Journal, 43(3), 515–526. Retrieved from https://ph01.tci-thaijo.org/index.php/KKUSciJ/article/view/249418