Partial Discharge Diagnosis and Localization in Underground Cable at Hin Kong Power Station, Nong Kae District, Saraburi, Thailand
Main Article Content
Abstract
This article presents an investigation of underground cable at Hinkong power station, Nongkae district, Saraburi province, Thailand which using Damped AC (DAC) Energizing and Conventional Partial Discharge (PD) Detection Method according to IEC 60270 and IEEE 400.3 as a regular maintenance program of Provincial Electricity Authority (PEA). The PD test has been performed over two underground power circuits in the duct bank, 12/20 kV - XLPE cable hosed in the HDPE pipe, length from switchgear to riser pole of 336 m and 368 m. The test result of the first circuit indicates the PDIV (Partial Discharge Inception Voltage) at voltage of around 17.1 kVpk (1Uo) at PD 2,250 pC which has Phase Resolved Partial Discharge (PRPD) corresponded to the characteristics of PD occurring from the internal discharged at a distance of approximately 282 m from the test location. The test result of the second circuit indicates the PDIV at the voltage of around 7.6 kVpk (0.4Uo) at PD 2,750 pC which has PRPD corresponded to the characteristics of PD occurring from the internal discharged at a distance of approximately 366 m from the test location
Article Details
The manuscript, information, content, picture and so forth which were published on Journal of Engineering, RMUTT has been a copyright of this journal only. There is not allow anyone or any organize to duplicate all content or some document for unethical publication.
References
Hauschild W. Critical review of voltage applied for quality-acceptance and diagnostic field tests on high-voltage and extra-high-voltage cable systems.IEEE insulation magazine. 2013 March/April.
Van Veen L. W. Comparison of measurementmethods for partial discharge measurement in power cables. Master thesis delft University of Technology.2014
Mashikian S M, Boone W. Guide for partial discharge testing of shielded power cable systems in a field environment.IEEE 400.3. 2006.
Bartnikas R. Partial discharges. Theirmechanism, detection and measurement.IEEE transactions on dielectrics and electrical insulation. 2002 Vol. 9.No.5.
Gulski E, Cichecki P, Wester F, Smit J,Bodega R, Hermans T, Seitz P. On-site testing and PD diagnosis of high voltage power cables. IEEE transactions on dielectrics and electrical insulation.2008; 15(6); 1691–700.
Kulick J, Law J D, Hulett H R. Guide for field testing of shielded power cable systems using VLF. IEEE 400.2 . 2004.
Gulski E. Insulation condition assessment of medium voltage power cables using on-site PD detection and analysis techniques. Delft University of Technology.
Engelstatter H. GRU_Test PD diagnosis ENG 20050125. SebaKMT, diagnosis seminar. 2004
Gotz D. Theory II influence to TDR analysis.2010.
Sangsangsa S. High voltage engineering 1.Department of Electrical Faculty of Engineering Chulalongkorn University 1st edition. 2004. (In Thai)
Illias H, Yuan S T, Bakar A H, Mokhlis H,Chen G, Lewin L P. Partial discharge patterns in high voltage insulation. IEEE international conference on power and energy. 2012.
Gulski E, Wester J F, Smit J J, Groot E. PD knowledge rules for insulation condition assessment of distribution power cables.Delft University of Technology.
Keller M. OWTS PD diagnosis. OWTS-M seminar, Baunach, Germany, Seba Dynatronic Mess- und Ortungstechnik GmbH. 2007