A Cable Terminator for Partial Discharge and Dielectric Loss Measurements
##plugins.themes.bootstrap3.article.main##
摘要
This paper presents a design of the cable connector used in partial discharge and dielectric loss tests. The body of the connector is constructed using the PVC and the oil is used as an insulating medium. In order to implement the connector, partial discharges and the dielectric loss (tan 8) of a cable are tested according to IEC standards. It is found that the cable connector proposed can give the satisfactory and reasonably accurate results from the measurements. In addition, the cost of the construction of the connector developed is cheaper than that of the commercial module.
##plugins.themes.bootstrap3.article.details##
The manuscript, information, content, picture and so forth which were published on Frontiers in engineering innovation research has been a copyright of this journal only. There is not allow anyone or any organize to duplicate all content or some document for unethical publication.
参考
Haefely catalogue "Cable test terminations"
Bungay E.W. and McAllister "Electric cables handbook " BSP Professional books, 2nd edition, 1990
Kreuger F.H. "Partial discharge detection in high voltage equipment" Delft University,1981
Chan J.C., Duffy P. and Hiivala L.J. "PD testing of solid dielectric cable' IEEE Electrical Insulation magazine, September/October 1991,pp. 9-20.