A Cable Terminator for Partial Discharge and Dielectric Loss Measurements
Main Article Content
Abstract
This paper presents a design of the cable connector used in partial discharge and dielectric loss tests. The body of the connector is constructed using the PVC and the oil is used as an insulating medium. In order to implement the connector, partial discharges and the dielectric loss (tan 8) of a cable are tested according to IEC standards. It is found that the cable connector proposed can give the satisfactory and reasonably accurate results from the measurements. In addition, the cost of the construction of the connector developed is cheaper than that of the commercial module.